For best operation, mount a CM-E1 in the hallway near each bedroom or office area. In addition, another CM-E1 may be
mounted just inside the door from the adjoining garage. Consider placing another detector in a bedroom or office that is
adjacent to a furnace room.
This product is intended for use in ordinary indoor locations of family living units and office workspaces. The CM-E1 is not designed to
measure compliance with Occupational Safety and Health Administration (OSHA) commercial or industrial standards. (UL 2034)
Do NOT mount the unit in the garage. Do NOT mount the CM-E1 where the normal ambient temperature is below 40°F
(4.4°C) or exceeds 100°F (37.8°C), or within 5 feet (1.5 meters) of a cooking or heating appliance.
INSTALLATION
1. As shipped, the CM-E1 faceplate is mounted on the enclosure's rear-housing component. This enclosure
configuration allows the unit to be surface mounted flush on a wall. Wiring is routed through an access area on the
base of the rear housing.
2. A thin mid-plate enclosure component is also supplied with the CM-E1. Using the supplied screws, this mid-plate
component is used to mount the CM-E1 on a 2 x 4 inch (5.08cm x 10.16 cm) switch box - single-gang or "handy",
provided by the installer. The CM-E1's faceplate component (with the detector attached) is then mounted on the mid-
plate component.
3. The detector may be installed on either a ceiling or a wall. If installed on a peaked, gabled, or sloped ceiling, it should
be located about 3 feet (1 meter) from the highest point. The unit can be placed vertically or horizontally on a wall, so
the information on the front of the CM-E1 can be read in a normal manner (not upside down). Do NOT mount the
CM-E1 in a corner. Use the same spacing as for smoke detectors-- 30 foot (9 meters) centers, 900 sq. feet (83 sq.
meters) per detector.
4. Electrical connections to the CM-E1 are made via the supplied six-conductor pigtail cable. The pigtail cable is first
connected to the control panel wiring by means of wire-nuts (refer to the diagrams for proper pigtail wiring). The
pigtail cable's connector then snaps into the mating connector on the back of the CM-E1 detector, allowing easy
installation and replacement of the CM-E1. For proper detector operation, ensure that the CM-E1 is connected to a
continuous source of power (not controlled by a wall switch). The CM-E1 current draw figures represent worst-case
conditions and will not vary as the applied DC voltage varies.
5. The alarm control panel zone inputs must be terminated with end of line resistors (E.O.L.R.), which are provided with
the panel.
6. When using the CM-E1 with normally closed initiating circuits, remove the jumper.
7. See wiring diagram for information below on connections of the CM-E1. Macurco™ recommends a minimum of 22
AWG wire for runs up to 200 ft. (6096 m), and 18 AWG wire for longer runs.