The relay of the CM-E1 is a dry contact and rated at 100mA, 40VDC. It is not suitable for fan control use. When
connecting the units to remote buzzers or other devices (all buzzers or "other devices" must be UL approved), make sure
that the load does not exceed the relay’s rating. External buzzers must be capable of generating a sound output greater
than 85 dBA at 10 ft (3.048 M).
Power Up
When the unit is turned on it performs a self-test, which activates the audible and visual alarms. If the self-test fails, or all the alarms
do not activate, do not use. Failure to do so may adversely affect product performance and result in sickness or death.
When the detector is first powered, the status light will alternate between RED and GREEN as the unit performs a 2-1/2
minute warm-up cycle and self-test procedure. The buzzer on the CM-E1 will cycle once, emitting its characteristic 4-chirp
tone. At the end of this 2-1/2 minute cycle, the status light will turn GREEN to indicate normal operation and air below the
danger levels of carbon monoxide. The alarm relay is not energized during the 2-1/2 minute warm-up cycle.